Abstract: As we all know, , AXE-10 Exchanger Power Uninterrupted Cut Over is a very challengeable work all the times to power engineers. It’s very difficult and risky, for power off or short circuit might happen if careless. In order to avoid hidden trouble in power cut over, increase safety factor and decrease power operation risk ,I designed and made a power cut over Chopper Switch. In fact ,it’s very effective, it can help us to finish our power cut over work safely、expediently and fast. The structure of Chopper Switch is simple and its cost is low. It could be universal in practice. It’s such a good helper for power cut over that it is worth to be promoted in practice.
Key words: exchanger power cut over;chopper switch; design and application
1設計背景
由于我公司需要淘汰岔河母局和飲泉模塊局兩套已老化的開(kāi)關(guān)電源,因此要將老開(kāi)關(guān)電源直流配電屏上所有的AXE-10交換機48 V電源線(xiàn)一根根地帶電割接到新運行的開(kāi)關(guān)電源高阻直流配電屏上,而且要求在割接過(guò)程中絕對不能掉電和短路,一定要確保通信的暢通。
通常AXE-10交換機高阻配電帶電割接的傳統過(guò)程是:用兩只帶有48 V直流電源的正負專(zhuān)用線(xiàn)卡分別卡破AXE-10交換機機框上兩根48 V正負電源線(xiàn)(相當于在其上面再并聯(lián)一個(gè)外加的48 V輔助電源),然后在老開(kāi)關(guān)電源高阻直流配電屏近端分別剪斷相應的交換機正負電源線(xiàn)(電源線(xiàn)剪斷后,該交換機機框由輔助電源供電,故不會(huì )阻斷),在進(jìn)行必要的絕緣包裹后,再將此電源線(xiàn)引至新開(kāi)關(guān)電源高阻直流配電屏,并接到相應的位置,然后合上對應的空開(kāi)或熔絲送電,最后松開(kāi)線(xiàn)卡,再繼續下一根電源線(xiàn)的割接。如圖1所示。但是,在這樣傳統的割接過(guò)程中存在以下幾點(diǎn)重大掉電和事故隱患:
(1) 如果卡得太輕,線(xiàn)卡就不能卡破交換機電源線(xiàn)的絕緣皮,此時(shí)的輔助電源并沒(méi)有真正并聯(lián)到交換機的電源線(xiàn)上,如果這時(shí)輕易剪斷電源線(xiàn),交換機就會(huì )掉電。相反,如果線(xiàn)卡卡得太重,則會(huì )嚴重損傷交換機的電源線(xiàn),為以后的維護工作帶來(lái)不利的影響。
(2) 如果不小心將正負電源線(xiàn)卡與交換機的電源線(xiàn)極性接反,則會(huì )發(fā)生嚴重的短路事故,輕則熔絲熔斷、交換機掉電,重則不僅交換機掉電,還會(huì )燒壞這一層機框的電路板,后果不堪設想。
(3) 如果48 V直流輔助電源與線(xiàn)卡直連,中間沒(méi)有隔離開(kāi)關(guān),正負線(xiàn)卡在松開(kāi)的狀態(tài)下,萬(wàn)一彼此相碰或碰到通信設備,都會(huì )引起短路打火,十分不安全;如果只對負線(xiàn)采取隔離措施(例如在負線(xiàn)上加一路空氣開(kāi)關(guān)),而“+”線(xiàn)卡與系統的“+”直連,由于線(xiàn)卡質(zhì)輕且位置不固定,容易碰到機房中通信設備的“-”,同樣也會(huì )造成短路事故。
2改進(jìn)后的割接工作原理及說(shuō)明
正是為了防止以上可以預見(jiàn)的事故隱患,本人對傳統的割接方法進(jìn)行了改進(jìn)(見(jiàn)圖2),并特地設計了專(zhuān)用割接閘刀(見(jiàn)圖3)。
改進(jìn)后的割接方法的原理及說(shuō)明如下:
(1)在割接開(kāi)始之前閘刀應處于分開(kāi)的位置。
(2)將閘刀按照正負極性接到輔助電源( 新電源或老電源的一路輸出)。
(3)LED4是輔助電源指示燈,只要輔助電源正常,發(fā)光二極管LED4(紅色)就會(huì )亮。
(4)當線(xiàn)卡“—”夾破交換機負電源線(xiàn)時(shí),輔助電源“+”端與線(xiàn)卡“-”間48 V電壓就會(huì )加在R2和LED2上,使LED2(綠色)發(fā)光。
(5)當線(xiàn)卡“+”夾破交換機正電源線(xiàn)時(shí),線(xiàn)卡“+”與輔助電源“-” 端間48 V電壓就會(huì )加在R3和LED3上,使LED3(黃色)發(fā)光。
(6)只有當“+” 、“-” 線(xiàn)卡都已分別正確夾破交換機正負電源線(xiàn)時(shí),LED1(綠色)才會(huì )發(fā)光。
(7)當不小心將正負電源線(xiàn)卡與交換機的電源線(xiàn)極性接反時(shí),LED1、LED2、LED3都不會(huì )亮,就會(huì )提醒操作人員進(jìn)行檢查,從而可以有效地防止由于極性接反(上述第二點(diǎn)事故隱患)而引起的重大事故。
(8)針對第三點(diǎn)事故隱患,故在本設計中采用“雙刀”單擲閘刀,可以同時(shí)隔離閘刀開(kāi)關(guān)前后正負線(xiàn)路,起到十分可靠的隔離作用,防止短路事故的發(fā)生。
(9)割接閘刀可以使用普通交流雙刀單擲閘刀,其規格(大?。摳鶕?shí)際負載電流的大小來(lái)進(jìn)行選配(在本例中選用30A)。
3 具體的割接操作步驟
具體的割接操作步驟如下:
(1)將割接閘刀的一端分別接至新直流配電屏的一路輸出熔斷器或開(kāi)關(guān)上,此時(shí)割接閘刀上發(fā)光二極管LED4(紅色)亮。
(2)找到到需要割接的電源線(xiàn),在交換機的近端將交換機電源線(xiàn)外層絕緣皮剖開(kāi)(要防止傷到內層絕緣皮),若原來(lái)電源線(xiàn)的正負線(xiàn)本來(lái)就是分開(kāi)的,那么這一步可以省去。
(3)此時(shí)要注意保證割接閘刀處于分開(kāi)的狀態(tài),將兩只線(xiàn)卡按照正負極性卡住交換機上的電源線(xiàn),并用內六角扳手擰緊線(xiàn)卡上的螺栓,將交換機電源線(xiàn)上的絕緣皮卡破,此時(shí)割接閘刀上的“破線(xiàn)通電”指示燈應亮起(注:“+”線(xiàn)卡破時(shí)LED3黃燈亮、“-”線(xiàn)卡破時(shí)LED2綠燈亮、正、負線(xiàn)均卡破時(shí)LED1綠燈也會(huì )同時(shí)亮起),然后合上割接閘刀。
(4)剪斷原來(lái)高阻直流配電屏上相應的愛(ài)立信電源線(xiàn)(注意:正負線(xiàn)要分別剪斷)
(5)將愛(ài)立信電源線(xiàn)上的絕緣皮抹長(cháng)一點(diǎn),超出里面的導線(xiàn)的長(cháng)度,再裹上絕緣膠帶。
(6)再將此電源線(xiàn)沿架空線(xiàn)槽放到新電源直流配電屏,并接到相應的直流配電空氣開(kāi)關(guān)。
(7)合上直流配電屏空氣開(kāi)關(guān)。
(8)分開(kāi)割接閘刀。
(9)松開(kāi)并取下夾子。
(10)用絕緣膠帶裹好電源線(xiàn)被卡傷處。
(11)其余電源線(xiàn)割接依此類(lèi)推,若線(xiàn)長(cháng)度不夠,則要用連接銅管壓接加長(cháng)電源線(xiàn),并做好絕緣。
(12)割接完畢后,需對交換機做全面檢查,觀(guān)察交換機有無(wú)告警出現。
(13)記錄、整理直流配電資料。
4 割接注意事項
割接注意事項如下:
(1)要嚴格按照割接步驟執行,先后次序不能顛倒,只有當新直流空氣開(kāi)關(guān)送上電后,才能將割接閘刀分開(kāi)。
(2)每割完一根電源線(xiàn)后務(wù)必打開(kāi)割接閘刀,防止夾子之間短路。
5 實(shí)際應用效果
我分公司于05年4月份對岔河母局和飲泉模塊局開(kāi)關(guān)電源進(jìn)行了割接,并使用了自行設計的電源割接閘刀,結果不僅大大提高了安全系數,降低了動(dòng)力操作風(fēng)險,而且割接效率也得到顯著(zhù)的提升,取得了事半功倍的效果,使我們能夠方便、安全、迅速地完成了上級下達的割接任務(wù)。此電源割接閘刀結構簡(jiǎn)單,成本低廉,非常實(shí)用,通用性強,也同樣適用于其它中、小負荷通信設備的帶電割接,是電源割接的好幫手,值得推廣應用。
交換機相關(guān)文章:交換機工作原理